Previous
Next
- ATESS HPS 50KW HYBRID INVERTER
- HPS50
KERNEL PARAMERERS
- Apparent Power: 55kVA
- Rated Voltage: 400V
- Rated Current: 72A
- Voltage Range: 360V~440V
- Rated Frequency: 50/60Hz
- AC Conection: 3/N/PE
- AC Input: 100kVA
- Battery voltage: 48V/96V/192V/240V/380V/400V
- Wave form: Pure Sign Wave
BASIC SYSTEM ARCHITECTURE
The following illustration shows basic application of this inverter. It also includes following devices to have a Complete running system – Generator or Utility – PV modules Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor type appliances such as refrigerator and air conditioner.
KEY PRODUCT FEATURES
- A comprehensive hybrid inverter solution.
- Customizable operational modes.
- Dry contact output: Facilitating remote control of DG.
- LCD touchscreen interface: Facilitating parameter setup and maintenance.
- Expandable configuration: Multiply capacity through parallel connection of four units.
- Redundant system backup: In case of failure, another inverter seamlessly takes over.
- Smooth transition: Ensuring continuous power supply.




TECHNICAL PARAMETERS
Mdoel | HPS30KW | HPS50KW | HPS100KW | HPS120KW | HPS150KW |
---|---|---|---|---|---|
AC (Grid-connected) | |||||
Apparent power | 33kVA | 55kVA | 110kVA | 132kVA | 165kVA |
Rated power | 30kW | 50kW | 100kW | 120kW | 150kW |
Rated voltage | 400V | ||||
Rated current | 43A | 72A | 144A | 173A | 217A |
Voltage range | 360V – 440V | ||||
Rated frequency | 50/60Hz | ||||
Frequency range | 45~55/55~65Hz | ||||
THDI | <3% | ||||
PF | 0.8lagging~0.8leading | ||||
AC connection | 3/N/PE | ||||
AC input | 60kVA | 100kVA | 200kVA | 240kVA | 240kVA |
AC(Off-grid) | |||||
Apparent power | 33kVA | 55kVA | 110kVA | 132kVA | 165kVA |
Rated power | 30kW | 50kW | 100kW | 120kW | 150kW |
Rated voltage | 400V | ||||
Rated current | 43A | 72A | 144A | 173A | 217A |
THDU | ≤2%linear | ||||
Rated frequency | 50/60Hz | ||||
Overload capability | 110%-10 mins 120%-1 min | ||||
DC (Battery and PV) | |||||
Max PV open-circuit voltage | 1000V DC | ||||
MAX PV power | 45kWp | 75kWp | 150kWp | 180kWp | 225kWp |
PV MPPT voltage range | 480V-800V DC | ||||
Battery voltage range at Max.charge power | 450V-600V | 500V-600V | 500V-600V | 517V-600V | 500V-600V |
Battery voltage range | 352-600V | ||||
Max.charge power | 45kw | 75kw | 150kw | 180kw | 225kw |
Max.discharge power | 33kW | 55kW | 110kW | 132kW | 165kW |
Max.charge current | 100A | 150A | 300A | 350A | 450A |
Max.discharge current | 93A | 156A | 313A | 374A | 467A |
General Information | |||||
Protection degree | IP20 | ||||
Noise emission | <65dB(A)@1m | ||||
Operating temperature | -25 °C~+55 °C | ||||
Cooling | Forced-air | ||||
Relative humidity | 0-95% non-condensing | ||||
Maximum altitude | 6000m (derate over 3000m) | ||||
Dimension (W/H/D) | 950/1860/750mm | 950/1860/750mm | 1200/1900/800mm | 1200/1900/800mm | 1200/1900/800mm |
Weight | 505kg | 610kg | 948kg | 1025kg | 1230kg |
Build-in transformer | Yes | ||||
Transfer between on/off grid | Automatic≤10ms | ||||
Standby consumption | <30w | ||||
Communication | |||||
Display | Touch screen | ||||
Communication | RS485/CAN | ||||
Certificate | |||||
Certificate | CE , MEA , PEA , EN 61000-6-4:2007+A1:2011 , EN61000-6-2:2005 , EN62109-1:2010 , EN62109-2:2011 |